SAT-13B Power Quality Analyzer
 

    SAT-13B Power quality analyzer designed and manufactured in reference to GB/T14549-93 Electrical Energy Quality Harmonic Power Quality Public Utility Grid National Standards IEC 61000-4-31 A Grade Standards is a special hand-held instrument for testing and analyzing operation quality of utility grid. It can provide har. analysis and power quality analysis in electrical operation for fully monitoring impact upon utility grid during starting and stopping large-sized electrical equipment. Meanwhile, it is equipped with a large-capacity memory for long term data collection testing and PC application software to upload data onto PC for various analyses.
Functions and Characteristics
Basic Measurement Function:


Functions and Characteristics:

Measure Voltage, current, Freq and record its change Tren.
Har. Measurement Function:
Measure 3-phase 4-wire (3-volt, 4-current) 1st~50th order and its THD. Record the change Tren of Har. in a certain order.
Power Measurement Function:
Measure 3-phase active power, apparent power, reactive power, PF and etc. of 3-phase 4-wire electrical system, and record change Tren of 3-phase active power.

Characteristics:

1. Small size, light weight and portable
2. High performance Li battery provides long-term power supply
3. Complete 3-phase troubleshooting tools: Measure actual parameters of each electrical system: Voltage, current, Freq, power, power consumption (Energy), unbalan. and flicker, har. and interhar., and catch such events as transient, interruption, fast Voltage change.

Typical Application:

① Front End Troubleshooting: Utilize screen to view fast fault diagnostics so as to restore normal operation of the system
② Predictive Maintenance: Perform testing and prevent Electrical Energy quality problem before shutdown
③ Service Quality: Check Electrical Energy quality at service line
④ Long-term Analysis: Test indiscoverable or intermittent fault
⑤ Load Study: Check the electrical system capacity before increasing load
⑥ Energy Evaluation: Perform quantized evaluation of Energy consumption before and after reformation, to verify effect of low Energy consumption equipment.

Technical Indexes:

Input Impedance: 1MΩ, 20pF
Measurement Range and Precision
1) Voltage: 1 V~700 V (true effective value)±1%
2) Current: 1A, 10A, 100A, 1000A (select corresponding probe) ±1%
3) Freq: 30~80Hz ±0.01Hz
4) Har. Measurement: 1st~50th order Voltage/current
Surging Current: 2000 A (select 1000 A current sensor)
Peak Voltage: 1000 V
Memory Space: 4M bytes
Display Screen: 320×240 Colour Graphics LCD
Communication Interface: USB

Table 1-1 Various Measurement Indexes:

Items

Measurable Range
Measurement Precision
Description
Voltage/Current/Freq
3-phase Voltage: 0~1000V (true effective value)
Zero-wire Voltage: 0~70V (true effective value)
3-phase Current: 0~1000 A (True effective value, select 1000 A current sensor)
Zero-wire current: 0~25 A (true effective value, select 25 A current sensor)
Freq: 30~80 Hz
Voltage: ±1%
Current: ±1%
Freq: ±0.5%
Here A phase Voltage Freq taken as measuring Freq
Har. Measurement
Voltage Har.: Total Har. +1st ~50th Har.
Current Har.: Total Har. +1st ~50th Har.
Voltage Har.: 1%
Current Har.: 1%
Power Measurement
Active Power: 0.01~10000 KW
Apparent Power: 0.01~10000 KVA
Idle Power: 0.01~10000 KVAR
PF: 0.00~1.00
Active Power Energy: 0.01~10000kWh
Apparent Power Energy: 0.01~10000kVAh
Idle Power Energy: 0.01~10000kVARh
Average PF: 0.00~1.00
Active Power: ±2%
Apparent Power: ±2%
Idle Power: ±2%
PF: ±0.1%
Active Power Electrical Energy: ±2%
Apparent Power Electrical Energy: ±2%
Idle Power Electrical Energy: ±2%
Average PF: ±0.1%
3-phase Unbalan.
Fundamental Voltage: 0~1000 V (true effective value)
Fundamental Current: 0~1000 A (true effective value)
Fundamental Freq: 30~80Hz
Phi: 0~360o
Unbalan. Factor: 0.0%~100%
Voltage: ±1%
Current: ±1%
Freq: ±0.5%
Phi: ±1%
Unbalan. Factor: ±2%
Here A phase Voltage Freq taken as measuring Freq
Monitor Record
Recordable Parameters:
3-Phase Voltage, 3-Phase Current, Zero-Wire Current, Voltage Har. (Total Har. +1st ~50th Har.), Current Har. (Total Har. +1st ~50th Har.), 3-Phase Unbalan., Active Power, PF

Same as above relevant items
99 hr data can be recorded at most per task. If various record parameters are selected, record time will be shortened as a result.
Abrupt Increase/Decrease
Abrupt Voltage Increase, Abrupt Voltage Decrease and Temporary Power-Cut
Record 200 events at most
Fluctuations
Voltage Fluctuations
0.1%~10.0%
Flickering
Short-term and Long-term Flicker
Digital Oscilloscope
3-phase Voltage, 4-wire current Tran Waveform
Max. Sampling Freq: 200KHz
Max. Sampling Freq: 100Hz