| SAT-13B
Power Quality Analyzer |
|
|
| |
 |
| SAT-13B
Power quality analyzer designed and manufactured in reference
to GB/T14549-93 Electrical Energy Quality Harmonic Power Quality
Public Utility Grid National Standards IEC 61000-4-31 A Grade
Standards is a special hand-held instrument for testing and
analyzing operation quality of utility grid. It can provide
har. analysis and power quality analysis in electrical operation
for fully monitoring impact upon utility grid during starting
and stopping large-sized electrical equipment. Meanwhile,
it is equipped with a large-capacity memory for long term
data collection testing and PC application software to upload
data onto PC for various analyses.
Functions and Characteristics
Basic Measurement Function:
Functions and Characteristics:
Measure Voltage, current, Freq and record its change
Tren.
Har. Measurement Function:
Measure 3-phase 4-wire (3-volt, 4-current) 1st~50th order
and its THD. Record the change Tren of Har. in a certain order.
Power Measurement Function:
Measure 3-phase active power, apparent power, reactive power,
PF and etc. of 3-phase 4-wire electrical system, and record
change Tren of 3-phase active power.
Characteristics:
1. Small size, light weight and portable
2. High performance Li battery provides long-term power supply
3. Complete 3-phase troubleshooting tools: Measure actual
parameters of each electrical system: Voltage, current, Freq,
power, power consumption (Energy), unbalan. and flicker, har.
and interhar., and catch such events as transient, interruption,
fast Voltage change.
|
Typical Application:
① Front End Troubleshooting: Utilize screen
to view fast fault diagnostics so as to restore normal
operation of the system
② Predictive Maintenance: Perform testing and prevent
Electrical Energy quality problem before shutdown
③ Service Quality: Check Electrical Energy quality at
service line
④ Long-term Analysis: Test indiscoverable or intermittent
fault
⑤ Load Study: Check the electrical system capacity before
increasing load
⑥ Energy Evaluation: Perform quantized evaluation of
Energy consumption before and after reformation, to
verify effect of low Energy consumption equipment.
Technical Indexes:
Input Impedance: 1MΩ, 20pF
Measurement Range and Precision
1) Voltage: 1 V~700 V (true effective value)±1%
2) Current: 1A, 10A, 100A, 1000A (select corresponding
probe) ±1%
3) Freq: 30~80Hz ±0.01Hz
4) Har. Measurement: 1st~50th order Voltage/current
Surging Current: 2000 A (select 1000 A current sensor)
Peak Voltage: 1000 V
Memory Space: 4M bytes
Display Screen: 320×240 Colour Graphics LCD
Communication Interface: USB
Table 1-1 Various Measurement Indexes:
| Items |
Measurable
Range |
Measurement
Precision |
Description |
| Voltage/Current/Freq |
3-phase Voltage:
0~1000V (true effective value)
Zero-wire Voltage: 0~70V (true effective value)
3-phase Current: 0~1000 A (True effective value,
select 1000 A current sensor)
Zero-wire current: 0~25 A (true effective value,
select 25 A current sensor)
Freq: 30~80 Hz
|
Voltage: ±1%
Current: ±1%
Freq: ±0.5% |
Here A phase Voltage
Freq taken as measuring Freq |
| Har. Measurement |
Voltage Har.: Total
Har. +1st ~50th Har.
Current Har.: Total Har. +1st ~50th Har.
|
Voltage Har.: 1%
Current Har.: 1% |
|
| Power Measurement |
Active Power:
0.01~10000 KW
Apparent Power: 0.01~10000 KVA
Idle Power: 0.01~10000 KVAR
PF: 0.00~1.00
Active Power Energy: 0.01~10000kWh
Apparent Power Energy: 0.01~10000kVAh
Idle Power Energy: 0.01~10000kVARh
Average PF: 0.00~1.00
|
Active Power:
±2%
Apparent Power: ±2%
Idle Power: ±2%
PF: ±0.1%
Active Power Electrical Energy: ±2%
Apparent Power Electrical Energy: ±2%
Idle Power Electrical Energy: ±2%
Average PF: ±0.1%
|
|
| 3-phase Unbalan. |
Fundamental Voltage:
0~1000 V (true effective value)
Fundamental Current: 0~1000 A (true effective
value)
Fundamental Freq: 30~80Hz
Phi: 0~360o
Unbalan. Factor: 0.0%~100%
|
Voltage: ±1%
Current: ±1%
Freq: ±0.5%
Phi: ±1%
Unbalan. Factor: ±2% |
Here A phase Voltage
Freq taken as measuring Freq |
| Monitor Record |
Recordable Parameters:
3-Phase Voltage, 3-Phase Current, Zero-Wire Current,
Voltage Har. (Total Har. +1st ~50th Har.), Current
Har. (Total Har. +1st ~50th Har.), 3-Phase Unbalan.,
Active Power, PF
|
Same as above relevant
items |
99 hr data can
be recorded at most per task. If various record
parameters are selected, record time will be shortened
as a result. |
| Abrupt Increase/Decrease |
Abrupt Voltage
Increase, Abrupt Voltage Decrease and Temporary
Power-Cut |
|
Record 200 events
at most |
| Fluctuations |
Voltage Fluctuations |
0.1%~10.0% |
|
| Flickering |
Short-term and
Long-term Flicker |
|
|
| Digital Oscilloscope |
3-phase Voltage,
4-wire current Tran Waveform |
Max. Sampling Freq:
200KHz
Max. Sampling Freq: 100Hz
|
|
|
|
| |
|
|