AITELONG Technology Co., Ltd
 
Data Transmission Testing
Optical Communication Testing
Communication Line Tester
Battery/UPS Testing And Maintenance Equipment
Resistance Testing
SAT-ACO Series Intellectualized AC Load
 
 
Functions & Features:

◆Set/adjust discharging power according to performance parameters and detection requirements.

◆Set discharging time,timing to automatic shut-off load,discharge off and alarm operator.

◆Set load voltage,over/under voltage and over current protection threshold value,it can shut off load,terminate discharging and alarm user automatically.

◆Set storage datasheet recording period optionally which must be more than the minimum period 6Seconds.

◆Large screen LCD display,friendly interface,English menu,display discharge power,time,power consumption,every phase load voltage,current,frequency and inner temperature information real timly.

◆Parallel operation function to carry out multi sets load operation by RS 485 communication.

◆Readjust discharg paremeters during discharging process.

◆Built-in storage function,save 10 groups of test data,which can be inquired,deleted and put into flash disk.

◆Start/stop discharging control by Serial port,and detect data real time operation etc;The storage data can be uploaded to PC by serial port or flash disk,and the upper computer’s software can analyze data and pattern and print report etc.

◆Thernal protetion function,it can turn off load,terminate discharging and alarm automatically when over temperature.

◆Power Fail Recovery function.

◆ Set at most 10 groups power,load process automatically according to the setting power and operation time after being turned on.

Technical Parameters:
Condition of Circumstance Working Temperature:(-20~55)℃
Storage Temperature:(-45~70)℃
Relative humidity:90%(40±2℃)
Atmospheric pressure:(70~106)kPa
External Dimensions(mm) 670×620×905mm
Weight 90kg
Working Voltage Single-phase AC220V±10%,50Hz
Load voltage Three-phase AC380V、Single-phase AC220V
Operating power Stand-alone:Max 100KW(Three-phase 380V)
Max 30KW(Singly-phase 220V)
Parallel Operation:Sum of all stand-alones’ max power
Discharging Time 0~(99 hours and 59 minutes)Contunuously Adjustable
Tempearature alarm & Threshold Value 75℃
Quantity of Parallel operation 1~99 sets
Recording Period 6~999 Seconds
Voltage measurement range AC 0~450V, Display Resolution:0.1V,Precision:±5‰
Current measurement range AC 0~200A, Display Resolution:0.1A,Precision:±1%
Frequency measurement range 40~60 Hz, Display Resolution:0.1Hz,Precision:±2‰
Power measurment range 0~100 kW, Display resolution:0.1kW,Precision:±1%
Temperature measurement range -20~100℃,Display resolution:1℃,precision:±1℃
Cooling mode FCT(Fan control Temperature)
Communication Mode RS232,RS485 and USB communication
Display mode LCD with high brightness and large screen
MTTF ≥50000h

Please click here to download datasheet