| SAT-IA
Series Storage Battery Intellectualized Activator |
|
|
| |
|
Functions:
·Cell
activation:
Perform cell activation
on the state of online floating charge or offline. Users
should set up activation and cycling times, single-activation
charge time, protective voltage parameters before activation;
it can display battery voltage, charge/discharge current,
charge/discharge capacity, charge/discharge time and etc;
users can set up activation cycling and also stop the
activation manually.
·Cell check discharge:
Perform constant current discharge
for cell. Users should set up discharge time, discharge
capacity, cut-off voltage and etc before discharge; it
can display discharge current, battery discharged capacity,
battery voltage, discharge time and etc; users can manually
stop the discharge.
·Cell charge:
When the battery is on the state
of online floating charge or offline, it can perform automatic
charge for battery, users should set up charge current,
charge time, cut-off voltage and etc, the instrument can
display charge current, battery charged capacity, battery
voltage, charge time and etc; users can manually stop
the discharge.
● Features
·Data
storage: large capacity. Save 10 groups of activation
data, 10 groups of check discharge data, and 10 groups
of charge test data. Users can query, delete and export
the data.
·With RS232 interface and USB
interface. users can perform long-term historical data
storage and analysis.
·When the instrument detects abnormal
phenomenon of battery or working is abnormal, it automatically
stops testing for protecting battery.
·The activation adopts integrated
design with monitoring unit and power unit. The monitoring
unit adopts high-speed A/D and D/A, and power unit adopts
new-type parts.
This software is English designed,
and it can automatically create voltage/current histogram,
curve chart, and test report (including Excel table and
WORD document).
● Technical
parameters
| Model |
SAT-IA02/10 |
SAT-IA02/20 |
SAT-IA0612/03 |
SAT-IA0612/10 |
SAT-IA2612/20 |
| Cell voltage measurement type |
2V |
6V/12V |
2V/6V/12V |
2V/6V/12V |
| Cell voltage measurement range |
0~3V |
6V:0.1~16V
12V:4~15V |
2V:0~3V 6V:4~8V
12V:4~15V |
2V:0~3V 6V:4~8V
12V:4~15V |
| Cell voltage resolution |
0.001V |
0.01V |
2V:0.001V 6V:0.01V
12V:0.01V |
2V:0.001V 6V:0.01V
12V:0.01V |
| Charge/discharge current working range |
2~100A |
5~200A |
6V:2~20A
12V:2~30A |
2V:2~100A 6V:2~20A
12V:2~30A |
2V:5~200A 6V:5~20A
12V:5~30A |
| Battery capacity check range |
20~1000Ah |
50~2000Ah |
6V:20~200Ah
12V:20~300Ah |
2V:20~1000Ah
6V: 20~200Ah
12V: 20~300Ah |
2V:50~2000Ah
6V: 50~200Ah
12V: 50~300Ah |
| Charge/discharge current control accuracy |
0.1A |
| Current testing accuracy |
1% |
| Voltage testing accuracy |
0.5% |
| Working voltage |
AC220±15% |
| Communication mode |
RS232 communication and
USB communication |
| Cooling mode |
Refrigeration by blast |
| Working environment |
Temperature: 0℃~40℃ Humidity:
20%~80%RH |
| Storage condition |
-20℃~70℃ package and storage |
| Display mode |
LCD with high brightness |
| External dimensions(L×W×H)mm |
365×210
×335 |
450×185
×515 |
365×210
×335 |
450×185
×515 |
450×190
×585 |
| Weight |
9kg |
20kg |
9kg |
22kg |
19.5kg |
| Carry method |
Portable type |
Portable type, move with
roller wheel |
|
|
| |
|
|