AITELONG Products
SAT-AMS Intelligent Battery Monitor


SAT-AMS
SAT-AMS Intelligent Battery Monitor
SAT-AMS is designed specifically for single-cell battery monitoring. One system includes TV modules, TC modules and one CM module, with continuous 24/7 online monitoring of battery voltage and temperature.
Contact Aitelong →SAT-AMS is designed specifically for single-cell battery monitoring. One system includes TV modules, TC modules and one CM module, with continuous 24/7 online monitoring of battery voltage and temperature.
Key Features
- One TV module monitors the voltage and temperature of one cell.
- Optically isolated serial port with MODBUS protocol, accessible by a UPS controller.
- String current and ambient temperature monitoring with a TC module.
- Automatic analysis, historical data storage and battery maintenance assessment with a CM module.
- Panel alarm indication and alarm reading over the serial bus.
- Operating parameters can be set over the serial bus.
- PC software manages multiple strings, real-time alarms and historical data.
- Easy installation without specialized training.
Applications
UPS, telecommunications, battery supplied applications, utilities, fire and safety systems, and remote monitoring.
| Compatible batteries | 2V, 6V or 12V |
| String voltage | 20–800V; ±(0.5% + 0.2V) |
| Cell voltage | 1.5–2.5V: ±(0.1% + 1mV); 9–15V: ±(0.1% + 10mV) |
| Battery temperature | 5°C–70°C; ±1.5°C |
| Ambient temperature | −10°C–70°C; ±0.5°C |
| String current | 0–500A; ±2% (full scale) |
| Operating environment | −5°C–50°C; 5%–90% RH |
| Storage environment | −10°C–70°C; 5%–90% RH |
| TV module power | Powered from the battery; less than 12mA (2V) or 4mA (12V) |
| TC module power | DC 8–13V, 2W |
| Converter power | DC 8–13V, 0.3W |
| CM module power | 85–264VAC or 100–370VDC, 15W |
| TV module interface | Serial port, MODBUS; supports 130 devices on each bus |
| TC module interface | Serial port, MODBUS |
| CM module interfaces | RS485 and Ethernet; MODBUS/RTU, MODBUS/TCP and SNMP |
| Insulation | 2000VAC |
| Protection | Test leads and power paths are fused |
| Installation | Paste on battery or rail mounting |
| Weight | TV module: 50g; TC module: 260g; CM module: 1.8kg |
| TV module dimensions | 38 × 61.45 × 21.2mm |
Options
Converter: connects applications without a CM module directly to a controller. PC software: reads and displays data from the CM module.